Merlin Gerin Compact range of MCCBs is the leading international brand. Compliance to all major international standards and tropicalisalion to withstand extreme climatic conditions has ensured its most preferred status in more than 130 countries all over the world.

The offered range comprises of the latest Compact NS series from 16 A to 630 A and Compact C from 800 A to 1250 A.

Designed to meet and also to exceed the requirements of latest standards
(IEC-947-2 / IS 13947-2), these mccb's offer wide range of special features with exceptional performance characteristics.

Service continuity :

The innovative 'roto-active' breaking principle is the heart of the latest NS range. Comprising of an unique double break, rotary contact system along with a pressure tripping unit, the reflex mechanism, it ensures exceptional current limitation. Total discrimination is achievable as a standard feature

Reliable protection :

The high levels of breaking capabilities is supported by a extensive range of tripping releases, both thermo-magnetic and electronic, with a host of user definable options for protection, monitoring, measurement and communication.

User friendly :

A modular construction along with a wide range of site-fittable common auxiliaries and add-on functional modules allows field conversion of the basic breaker to a multifunctional one as per user requirement. Rationalization dimensions has enabled availability of 8 breaker ratings with 3 breaking capacities in just 3 frame sizes with uniform cut-outs/mounting dimensions.

Total Safety :

All compact circuit breakers are suitable for isolation as defined by IEC947-2, even when equipped with motor mechanism or rotary handle. Locking in the open position (maximum 3 padlocks or key lock) ensures total safety during maintenance.

Roto - Active mechanism :

The Roto-active breaking system provides the circuit breakers with a high level breaking capacity in a confined space, and an outstanding disconnection and endurance performance.

Each device contains 3 or 4 identical breaking units each of which is sealed in a thermoset polyester chamber. The breaking mechanism comprises two contacts in series with an intermediate contact mounted on a rotating pivot. At high fault currents, due to magnetic repulsion produced by current reversal phenomenon, two arcs are generated. The rotating movement directs the arc into the arc chutes and ensures rapid extinction.

The reflex tripping system consists of piston trip unit which is connected to the arc chute chamber of the breaking units. The gases produced during fault interruption is directed to the piston unit which directly actuates the breaker opening mechanism, the impulsion time is minimum and faults of 15kA are cleared in 2 milisecs.

 

 

 

 

 

Moulded Case Circuit Breakers

Moulded Case
Circuit Breakers

 

 

 

 

 

 

 

 

 

Compact NS
breaking unit

TECHNICAL SPECIFICATION :

Compact circuit breakers
NS100
NS 160
NS 250
NS 400
NS 630
C 801
C 1001
C1251
number of Poles
3, 4 (*)
3, 4 (*)
3, 4 (*)
3, 4
3, 4
3, 4
3, 4
3, 4
rated current (A)
In
40°C
100
160
250
400
630
800
1000
1250
protection against overcurrents (A)
Ir
setting
current
12.5..100
12.5..160
12.5..250
160..400
250
..630
320
..800
400..1000
500..1250
rated insulation voltage (V)
Ui
750
750
750
750
750
750
750
750
rated insulation withstand voltage (V)
uimp
8
8
8
8
8
8
8
8
rated operational voltage (V)
Ue
AC 50/60
Hz
690
690
690
690
690
690
690
690
DC
500
500
500
500
500
N
H
N
H
N
H
N
H
N
H
N
H
N
H
N
H
ultimate breaking capacity (kA rms)
Icu
AC 50/
60 Hz
380/
415 V
25
70
36
70
36
70
45
70
45
70
50
70
50
70
50
70
service breaking capacity
Ics
(% Icu)
100%
100%
100%
100%
100%
100%
100%
100%
100%**
100%**
50%
50%
50%
50%
50%
50%
utilization category
A

A

A
A
A
A
A
A
A
A
B
B
B
B
B
B
short-time withstand current 1 sec
Icw
kA rms
--
--
--
--
--
--
--
--
--
--
12
12
15
15
15
15
endurance (C-O cycles)
mechanical
50000
40000
20000
15000
15000
15000
15000
15000
elec
trical
440
V-In
30000
20000
10000
6000
4000
1500
1500
1500
dimensionsL x H x D (mm)
2/3 poles,
fixed FC
105x161
x86
105x161
x86
105x161
x86
140x255
x110
140x255
x110
210x374
x172
210x374
x172
210x374
x172
4 poles,
fixed, FC
140x161
x86
140x161
x86
105x161
x86
185x255
x100
185x255
x100
210x374
x172
280x374
x172
280x374
x172
weight (kg)
3 poles,
fixed, FC
1.6
1.6
1.9
6.0
6.0
13.0
13.0
13.0
4 poles,
fixed, FC
2.1
2.1
2.3
7.8
7.8
17.0
17.0
17.0

*2 Pole only for N Type
** For operational voltage upto 500v

TRIP UNIT SETTINGS :

Trip Units
TMD
STR22SE
STR23SE
STR53UFET
STR25DE
STR55UET
Protection
overload protection threshold Ir (A)
0.8...1 xIn
0.4...1xIn
0.4...1xIn
0.4...1xIn
0.4...1xIn
0.4...1xIn
Tripping Time (overload), tr (sec) @ 6xir
-
5...7.5
5...7.5
5 settings
6...7.5
6 settings
Short Circuit Protection Threshold, Im (A)
Fixed
2...
10xIr
2...
10xIr
1.5...
10xIr
1.5...10xIr
1.5...10xIr
Time delay (short circuit), tm (msec)
--
Fixed (£40)
Fixed (£40)
4 settings
Fixed (£60)
4 settings
Instantaneous Protection Threshold, I (A)

--

11xIn
11xIn
1.5...11xIn
-
2....15xIn
Earth Fault Protection Threshold, Ih (A)
--
--
--
0.2...1xIn
--
0.2...0.6xIn
Earth Fault tripping delay, the (sec)
--
--
--
4 settings
--
4 setting

Note : Adjustable Neutral Protection option is available in all trip units except TMD

 

 

Air Circuit Breaker

MASTERPACT MERLIN GERIN

Masterpact Presentation :

Masterpact circuit breakers are used to protect and control low-voltage distribution systems. They may be installed in main LV switchboards (incoming units, main and secondary outgoings). Masterpact is a complete range offering a large selection of performance levels :

  • ratings from 800 to 6300A, AC, from 1000 to 8000 A DC;
  • breaking capacity from 40 to 150 kA rms;
  • operational voltages 690 V Ac, 1000 V DC.

Many versions :

  • 3 or 4 poles;
  • fixed or drawout versions;
  • current-limiting version up to 2500 A;
  • Wide range of control units offering multiple functions.

Circuit breakers designed for all applications

  • 1000 V AC version;
  • DC version;
  • anti-corrosion version;
  • source-changeover version;
  • merchant-marine and military versions. Masterpact circuit breakers comply with all major international standards and meet T2 tropicalisation criteria.

Front face :

  1. opening push-button (O)
  2. closing push-button (I)
  3. keylock for "connected", "disconnected" or "test" position
  4. door interlock
  5. stored-energy-mechanism charging handle
  6. operations counter
  7. "open" position keylock
  8. racking handle storage
  9. functional position indicator "connected", "test" and"disconnected"
  10. controls on fixed chasis (accessible with cubicle door closed)
  11. padlocking facilities for "connected", "disconnected" or "test" position
  12. stored-energy-mechanism status indicator
  13. main-contact position indicator
  14. fault-trip indicator/breaker reset button

Reduced dimensions :

  • AC circuit breakers ;
    • a single frame size from 800 to 3200 A;
    • common height and depth from 800 to 6300 A;
  • DC circuit breakers:
    • common height and length from 1000 to 8000A for operational voltages up to 500 V DC,
    • common height and length from 1000 to 4000A for operational voltages greater than 500 V DC.

Masterpact : functions and characteristics
circuit breaker selection M08 to M10

Masterpact circuit breakers
M08
M10
number of poles
3, 4
3, 4
electrical characteristic as per IEC 947-2 and EN 60947-2
rated current (A)
In
40 °C
800
1000
rating of 4th pole (A)
800
1000
rating insulation voltage (V)
Ui
1000
1000
rated impulse withstand voltage (V)
Uimp
8000
8000
rated operational voltage (V)
Ue
AC 50 /60 Hz
690
690
type of circuit breaker
N1
H1
H2
L1
N1
H1
H2
L1
ultimate breaking capacity (1)
(kA rms)
Icu
AC 50/
60 Hz
220/
415V
40
65
100
130
40
65
100
130
440V
40
65
100
110
40
65
100
110
500/
690 V
40
65
85
65
40
65
85
65
service breaking capacity
Ics
(% Icu)
100%
100%
100%
100%
100%
100%
100%
100%
short-time
withstand current
(kA rms)
Icw
AC 50/
60/ Hz
0.5 s
40
65
65
12
40
65
65
12
1 s
30
50
50
12
30
50
50
12
3 s
22
32
32
12
22
32
32
12
making capacity
(kA peak)
Icm
AC 50/
60/ Hz
220/
415 V
84
143
220
286
84
143
220
286
440 V
84
143
220
242
84
143
220
242
500/
690 V
84
143
187
143
84
143
187
143
electrodynamic withstand (kA peak)
84
143
143
24
84
143
143
24
utilisation category
B
B
B
B
B
B
B
B
suitability for isolation
*
*
break time
25 to 30 ms without intentional time delay and 9 ms for type L1
closing time
70 ms

endurance
(c-o cycles)
x 1000

mechanical
with maintenance
20
20
20
15
20
20
20
15
no maintenance
10
10
10
10
10
10
10
10
electrical
no maintenance
440
V-In
10
10
10
2.5
10
10
10
2.2
690
V-In
10
10
10
2.5
10
10
10
2.2
motor
control
(AC3-
947-4)(2)
690V
10
10
10
-
10
10
10
-
electrical characteristics as per standard Nema AB1
breakng capacity (kA)
480 V
40
65
100
-
40
65
100
-
600 V
40
65
65
-
40
65
65
-
projection
200 to 800 (3)    
200 to 1000 (3)
control
unit
protection type
instantaneous
STR 18 M
*
*
*
*
*
*
distribution
STR 28 D
*
*
*
*
*
*
selective
STR 38 S
*
*
*
*
*
*
*
*
universal
STR 58 U
*
*
*
*
*
*
*
*
STR 68 U
*
*
*
*
*
*
*
*
installation and connection
connection              front and rear connections
version
drawout
*
*
fixed
*
*
indication and measurement auxiliaries
auxiliary switches
*
*
electronic trip unit related functions
*
*
control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
*
*
motor machines (MCH)
*
*
operation counter (CDM)
*
*
installation and connection accessories
locking by padlock or keylock/mismatch protection
*
*
safety shutters (VO)
*
*
interphase barriers (EIP)
*
*
partitioning fixture (AC)
*
*
arc-chute cover (CC)
*
*
terminal-block cover (CB)
*
*
door frame (CDP)
*
*
transparent cover (CCP)
*
*

 

Masterpact : functions and characteristics
circuit breaker selection M12 to M16

Masterpact circuit breakers
M12
M16
number of poles
3, 4
3, 4
electrical characteristic as per IEC 947-2 and EN 60947-2
rated current (A)
In
40 °C
1250
1600
rating of 4th pole (A)
1250
1600
rating insulation voltage (V)
Ui
1000
1000
rated impulse withstand voltage (V)
Uimp
8000
8000
rated operational voltage (V)
Ue
AC 50/60 Hz
690
690
type of circuit breaker
N1
H1
H2
L1
N1
H1
H2
L1
ultimate breaking capacity (1)
(kA rms)
Icu
AC 50/
60 Hz
220/
415V
40
65
100
130
40
65
100
130
440V
40
65
100
110
40
65
100
110
500
/690V
40
65
85
65
40
65
85
65
service breaking capacity
Ics
(% Icu)
100%
100%
100%
100%
100%
100%
100%
100%
short-time
withstand current
(kA rms)
Icw
AC 50/
60/ Hz
0.5 s
40
65
65
12
40
65
65
17
1 s
30
50
50
12
40
50
50
17
3 s
22
32
32
12
22
32
32
12
making capacity
(kA peak)
Icm
AC 50/
60/ Hz
220/
415V
84
143
220
286
84
143
220
286
440 V
84
143
220
242
84
143
220
242
500/
690V
84
143
187
143
84
143
187
143
electrodynamics withstand (kA peak)
84
143
143
24
84
143
143
34
utilisation category
B
B
B
B
B
B
B
B
suitability for isolation
*
*
break time
closing time

endurance
(c-o cycles)
x 1000

mechanical
with maintenance
20
20
20
15
20
20
20
15
no maintenance
10
10
10
10
10
10
10
10
electrical
no maintenance
440V-In
10
10
10
2.5
10
10
10
2.2
690V-In
10
10
10
2.5
10
10
10
2.2
motor
control
(AC3-
947-4)(2)
690V
10
10
10
-
10
10
10
-
electrical characteristics as per standard Nema AB1
braking capacity (kA)
480V
40
65
100
-
40
65
100
-
600V
40
65
65
-
40
65
65
-
protection
200 to 1250 (3)
200 to 1600 (3)
control
unit
protection
type
instantaneous
STR 18 M
*
*
*
*
*
*
distribution
STR 28 D
*
*
*
*
*
*
selective
STR 38 S
*
*
*
*
*
*
*
*
universal
STR 58 U
*
*
*
*
*
*
*
*
STR 68 U
*
*
*
*
*
*
*
*
installation and connections
connection
version
drawout
*
*
fixed
*
*
indication and measurement auxiliaries
auxiliary switches
*
*
electronic trip unit related functions
*
*
control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
*
*
motor mechanism (MCH)
*
*
operation counter (CDM)
*
*
installation and connection accessories
locking by padlock or keylock/mismatch protection
*
*
safety shutters (VO)
*
*
interphase barries (EIP)
*
*
partitioning fixture (AC)
*
*
arc-chute cover (CC)
*
*
terminal-block cover (CB)
*
*
door frame (CDP)
*
*
transparent cover (CCP)
*
*

 

Masterpact : functions and characteristics
circuit breaker selection M20 to M25

Masterpact circuit breakers
M20
M25
number of poles
3, 4
3, 4
electrical characteristic as per IEC 947-2 and EN 60947-2
rated current (A)
In
40 °C
2000
25000
rating of 4th pole (A)
2000
25000
rating insulation voltage (V)
Ui
1000
1000
rated impulse withstand voltage (V)
Uimp
8000
8000
rated operational voltage (V)
Ue
AC 50/
60 Hz
690
690
type of circuit breaker
N1
H1
H2
L1
N1
H1
H2
L1
ultimate breaking capacity (1)
(kA rms)
Icu
AC 50/
60 Hz
220/
415V
55
75
100
130
55
75
100
130
440V
55
75
100
110
55
75
100
110
500/
690V
55
75
85
65
55
75
85
65
service breaking capacity Ics
(% Icu)
100%
100%
100%
100%
100%
100%
100%
100%
short-time
withstand current
(kA rms)
Icw
AC 50/
60/ Hz
0.5s
55
75
75
17
55
75
75
17
1 s
55
75
75
17
55
75
75
17
3 s
50
57
57
17
50
75
75
17
making capacity
(kA peak)
Icm
AC 50/
60/ Hz
220/
415V
121
165
220
286
121
165
220
286
440V
121
165
220
242
121
165
220
242
500/
690V
121
165
187
143
121
165
187
143
electrodynamics withstand (kA peak)
121
165
165
34
121
165
165
34
utilisation category
B
B
B
B
B
B
B
B
suitability for isolation
*
*
break time
25 to 30 ms without intentional time delay and 9 ms for type L1
closing time
70 ms
endurance (c-o cycles) x 1000
mechanical
with maintenance
15
15
15
15
15
15
15
15
no maintenance
10
10
10
10
10
10
10
10
electrical
no maintenance
440V -In
9
9
9
2
8
8
8
1.8
690
V -In
7
7
7
2
6
6
6
1.8
motor
control
(AC3-
947-4)(2)
690V
7
7
7
-
6
6
6
-
electrical characteristics as per standard Nema AB1
braking capacity (kA)
480V
55
75
100
-
55
75
100
-
600V
55
75
75
-
55
75
75
-
protection
200 to 2000 (3)
300 to 2500 (3)
control unit instantaneous STR 18 M
*
*
*
*
*
*
protection
type
distribution STR 28 D
*
*
*
*
*
*
selective STR 38 S
*
*
*
*
*
*
*
*
universal STR 58 U
*
*
*
*
*
*
*
*
STR 68 U
*
*
*
*
*
*
*
*
installation and connections
connection
front and rear connections
version drawout
*
*
fixed
*
*
indication and measurement auxiliaries
auxiliary switches
*
*
electronic trip unit related functions
*
*
control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
*
*
motor mechanism (MCH)
*
*
operation counter (CDM)
*
*
installation and connection accessories
locking by padlock or keylock/
mismatch protection
*
*
safety shutters (VO)
*
*
interphase barries (EIP)
*
*
partitioning fixture (AC)
*
*
arc-chute cover (CC)
*
*
terminal-clock cover (CB)
*
*
door frame (CDP)
*
*
transparent cover (CCP)
*
*

 

Masterpact : functions and characteristics
circuit breaker selection M32 to M40

Masterpact circuit breakers
M32
M40
number of poles
3, 4
3, 4
electrical characteristic as per IEC 947-2 and EN 60947-2
rated current (A)
In
40°C
3200
4000
rating of 4th pole (A)
3200
4000
rating insulation voltage (V)
Ui
1000
1000
rated impulse withstand voltage (V)
Uimp
8000
8000
rated operational voltage (V)
Ue
AC 50/60 Hz
690
690
type of circuit breaker
H1
H2
H1
H2
ultimate breaking capacity (1)
(kA rms)
Icu
AC 50/60 Hz
220/415V
75
100
100
150
440 V
75
100
75
100
500/690 V
75
85
75
85
service breaking capacity
Ics
(% Icu)
100%
100%
100%
100%
short-time withstand current (kA rms)
Icw
AC 50/60/Hz
0.5 s
75
75
75
75
1 s
75
75
75
75
3 s
75
75
75
75
making
capacity
(kA peak)
Icm
AC 50/60/Hz
220/415 V
265
220
165
220
440 V
165
220
165
220
500/690 V
165
187
165
187
electrodynamics withstand (kA peak)
165
165
165
165
utilisation category
B
B
B
B
suitability for isolation
*
*
break time
25 to 30 ms without intentional time delay and 9 ms for type L1
closing time
70 ms
80 ms
endurance
(c-o cycles)
x 1000
mechanical
with maintenance
15
15
10
10
no maintenance
10
10
5
5
electrical
no maintenance
440V - In
4
4
3
3
690V - In
2.6
2.6
2.5
2.5
motor
control
(AC3-947
-4)(2)
690V
2.6
2.6
2.5
2.5
electrical characteristics as per standard Nema AB1
braking
capacity (kA)
480V
75
100
75
100
600V
75
75
75
75
Protection
600 to 3200
2000 to 4000
control unit
instantaneous
STR 18 M
*
*
*
*
protection type
distribution
STR 28 D
*
*
*
*
selective
STR 38 S
*
*
*
*
universal
STR 58 U
*
*
*
*
STR 68 U
*
*
*
*
Installation and connections
connection
front and rear connections
rear connections
version
drawout
*
*
fixed
*
*
indication and measurement auxiliaries
auxiliary switches
*
*
electronic trip unit related functions
*
*
control auxiliaries
auxiliary releases (MN, NMR, MX, XF)
*
*
motor mechanism (MCH)
*
*
operation counter (CDM)
*
*
installation and connection accessories
locking by padlock or keylock/mismatch protection
*
*
safety shutters (VO)
*
*
interphase barries (EIP)
*
* (3P only)
partitioning fixture (AC)
*
*
arc-chute cover (CC)
*
*
terminal-clock cover (CB)
*
*
door frame (CDP)
*
*
transparent Cover (CCP)
*
*

 

Masterpact : functions and characteristics
circuit breaker selection M50 to M63

Masterpact circuit breakers
M50
M63
number of poles
3, 4
3, 4
electrical characteristic as per IEC 947-2 and EN 60947-2
rated current (A)
In
40 °C
5000
6300
rating of 4th pole (A)
2500 (5)
3200
rating insulation voltage (V)
Ui
1000
1000
rated impulse withstand voltage (V)
Uimp
8000
8000
rated operational voltage (V)
Ue
AC 50/60 Hz
690
690
type of circuit breaker
H1
H2
H1
H2
ultimate
breaking
capacity
(1) (kA rms)
Icu
AC 50/60 Hz
220/
415V
100
150
100
150
440 V
100
150
100
150
500/
690 V
85
85
85
85
service breaking capacity
Ics
(% Icu)
100%
100% (4)
100%
100% (4)
short-time
withstand
current
(kA rms)
Icw
AC 50/60/Hz
0.5 s
100
100
100
100
1 s
100
100
100
100
3 s
100
100
100
100
making
capacity
(kA peak)
Icm
AC 50/60/ Hz
220/
415 V
220
330
220
330
440 V
220
330
220
330
500/
690V
187
187
187
187
electrodynamics withstand (kA peak)
220
220
220
220
utilisation category
B
B
B
B
suitability for isolation
*
*
break time
25 to 30 ms without intentional time delay and 9 ms for type L1
closing time
80 ms
endurance
(c-o cycles)
x 1000
mechanical
with maintenance
10
10
10
10
no maintenance
5
5
5
5
electrical
no
maintenance
440 V-In
3
3
2
2
690 V-In
2.5
2.5
1.5
1.5
motor
control
(AC3-
947-4)(2)
690 V
2.5
2.5
1.5
1.5
electrical characteristics as per standard Nema AB1
braking capacity (kA) 480 V
100
125
100
150
600 V
100
100
100
100
protection
2000 to 5000
2000 to 6300
control unit instantaneous
STR 18 M
*
*
*
*
protection
type
distribution
STR 28 D
*
*
*
*
selective
STR 38 S
*
*
*
*
universal
STR 58 U
*
*
*
*
STR 68 U
*
*
*
*
installation and connections
connection
rear connections
version drawout
*
*
fixed
* (3P only)
indication and measurement auxiliaries
auxiliary switches
*
*
electronic trip unit related functions
*
*
control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
*
*
motor mechanism (MCH)
*
*
operation counter (CDM)
*
*
installation and connection accessories
locking by padlock or keylock/mismatch protection
*
*
safety shutters (VO)
*
*
interphase barries (EIP)
*
*
partitioning fixture (AC)
*
*
arc-chute cover (CC)
*
*
terminal-clock cover (CB)
*
*
door frame (CDP)
*
*
transparent Cover (CCP)
*
*

 

Miniature Circuit Breakers, Residual Current Circuit Breakers

MULTI 9

Miniature Circuit Breakers C 60H, 10kA, IEC 898-1995 :

In the industrial, commercial & residential sectors, final electrical distribution needs are continuously evolving; improved operating safety & continuity of service, greater convenience, operating cost management...

Merlin Gerin's MULTI 9 breakers have been designed to continually adapt to these evolving needs using new innovative solutions.

A COMPLETE MODULAR RANGE

  • Multi 9 is not just a name. The significance of '9' is most important for design, as the width of each module is in multiples of 9mm.
  • Dinrail fitment through an easy snap - on action coupled with auxiliaries viz. shunt trip, undervoltage release, auxiliary contact - all adaptable in field without any special tools and without interrupting power supply.

HIGHER PERFORMANCE IN A SMALLER PACKAGE

  • Merlin Gerin"Multi 9" C60H MCBs are current limiting type with a breaking capacity of 10kA as per the latest Standards IEC 898 (1995) / IS 8828 (1996).
  • These MCBs provide reliable protection of circuits against overload & shortcircuit - ideal for industrial, commercial & residential installations.
  • Tripping curves (B, C & D type) are stabilized to offer repeat accuracy.

FLEXIBILITY

  • Multi 9 C60H MCB can be used as an incoming breaker and easily co-ordinated with Merlin Gerin MCCBs through effective discrimination & cascading.
  • No line/load restriction ensures that any of the terminals can be used as incoming or outgoing.
  • Suitable for 400 Hz as well ad DC applications. (in addition to 50Hz)
  • Can be mounted easily in any of the regular distribution boards.

ENERGY SAVING

  • IEC 898-1995 / IS8828-1996 have recognised the growing importance of limiting power loss in switchgear devices and stipulated maximum permissible power loss values per pole for MCBs. Merlin Gerin C60H MCBs having power loss figures of 40-75% of the stipulated values contribute significantly to this energy saving.

SAFETY

  • The terminal screws are well recessed to avoid any unpleasant accidents. The terminals are "finger safe" to IP20 degree of protection.
  • Positive contact indication confirms the state of the device.

AUXILIARIES / ACCESSORIES The only MCB in India with :

  • Shunt Trip
  • Undervoltage Release
  • Auxiliary Contact
  • Terminal Shields

TECHNICAL DATA

Specification : IEC 898-1995 / IS 8828 - 1996
Current rating : 1 to 63 A
Voltage rating : 230/415 V AC
Breaking capacity : Icn Ultimate breaking capacity

 

Rating (A)
Type
Voltag (V)
Breaking
Capacity (A)
1 to
63A
1P
230/240
10000
2, 3, 4 P
400/415
10000

Number of operating cycle (O-C) : 20000
Tripping Characteristics

  • B Curve : The magnetic releases operate between 3 and 5 In.
  • C Curve : The magnetic releases operate between 5 and 10.
  • D Curve : The magnetic releases operate between 10 and 14.

Power loss per pole (W) :

Rated Current IN
As Per IEC 898-1995
C60H
<10
3.0
2.0
10 < In < 16
3.5
2.6
16 < In < 25
4.5
3.0
25 < In < 32
6.0
3.5
32 < In < 40
7.5
4.6
40 < In < 50
9.0
4.5
50 < In < 63
13.0
5.5

Impulse withstand voltage (Uimp.) : 6kV

Topicalization : Treatment 2 (relative humidity 95% AT 55°C)

Weight
Type
1P
2P
3P
4P
g
110
220
340
450

Tropicalization : Treatment 2 (Relative Humidity 95% at 55°C

Connections : To Ensure contact surface area tunnel terminals for rigid cables up to :
25mm2 for rating < 25A
35 mm2 for rating 32 to 63 A

C60H Electrical Auxiliaries :

C60 auxiliaries enable remote tripping or remote indication of the ON/OFF position of an MCB.

They are mounted by clipping on the left hand side of the MCB.

REMOTE INDICATION :

OF Auxiliary Switch :

  • A changeover switch which acts as an indicating or control device to monitor the "ON" or "OFF" position of an MCB.
  • Test function

SD Alarm Switch :

  • An indicating device which monitors the tripping of an MCB. This device offers the following
    • A red flag trip indicator
    • Ability to reset without closing the MCB.
    • Test function.
  • Breaking capacity of contacts :
Voltage (V)
(A)
415 V AC
3
240 V AC
6
24 V DC
6

REMOTE TRIPPING :

MX + OF Shunt Trip Release :

  • Enable the MCB to be tripped from a remote location.
  • Allows remote indication of the "OFF" or "ON" position of the MCB by using the same voltage as the one feeding the shunt trip (terminals 12 and 14)
  • Is equipped with a cut-off switch in series with the coil.
  • All shunt trip release devices are equipped with a red flag trip indicator

MN Undervoltage Release :

  • Enables the miniature circuit breaker to be tripped either when the voltage drops or by operation of the"OFF" push button of a remote device tripping between 70 and 35% Un' closing 85%Un'
  • Prevents the MCB from being switched "ON" again if the undervoltage release supply is not present.
  • MNS under voltage release (time delayed), allows micro breaks < 200 ms without effects.
  • All undervoltage releases are equipped with a red flag trip indicator.

Consumption of releases :

(V)
(W or VA)
MX
415 V AC
pickup
120
220/240 V AC
pickup
50
24 V AC - DC
pickup
120
MN
220/240 V AC
hold
4.1
MN
220/240 V AC
hold
4.1